Express the Subject another way, in a Google search with AI:
may gravity-drain condensate lines loop with a low point?
Yes, a gravity-drain condensate line can include a loop with a low point, as long as the overall slope of the line still allows for proper drainage by gravity; the low point essentially acts as a "trap" to collect any debris or sediment that might otherwise clog the line further down.
This result is correct. A trap may exist. It is not commanded or desirable. Condensate is acidic and foul, and over years unflushed, can be plug the line. In usual PVC, the fouling is not visible.
Most HVAC mechanics think a trap is MANDATORY, and will glue-in this PVC trap. They will then plumb this to a transfer pump.
This is the starting condition of a situation I have improved. See the undesirable PVC trap in the upper drain line of an air conditioning heat exchanger. The high-efficiency gas furnace condensate drain dumps directly to the pan of an ugly condensate pump. The pump pushes foul water up and over thirty feet to dump outside through a drilled hole in a rim joist.
There was never a need for the PVC trap.
All will be rearranged except the supply registers and their approaching in-wall ducts.
Now toss the PVC pipes and dump as trash. See a convenient plumbing drain that will accept gavity drain of condensate via a new P-trap.
With this arrangement of joining the two condensate paths, a trap exists in the furnace condensate line. I know it is nonsense that this could alter the dripping-down in the exhaust pipes or affect furnace performance, I will eliminate the trap.
As the minimum required for all drain piping, and as limited by availble elevation change, I maintained a steady 1/4 inch per foot downward slope to disccharge atop a P-trap
I then swapped out the furnace-drain plastic 1/2" MPT x 3/4" barb fitting for brass, to stop a flow pouring along the barbs.Unbelievably, the barbs are formed as spiral threads. I can't just return the fitting to Home Depot. I have reported a manufacturing error, homedepot.com, Feedback, asking a product recall. I believe the pipe threads also leak unavoidably from roundedness and inability to develop sealing pressure of engagement. Cast polypropylene may be always inappropriate for fluid hose fittings.
This is the homedepot.com product image. Do you see the spiral threading of the barbs?
4.5 stars in 56 reviews. There is no means of offering my own review.
This diversion from my Subject illustrates my outside-the-box nature. I readily see foolishness and worse, and can't abide it. That makes me unemployable.
Here are rival and contradicting Google AI search results:
Yes, a condensate line must have a trap, especially if the drain is under negative pressure, as it prevents conditioned air from being blown back into the living space and is crucial for proper drainage and system efficiency; essentially, a trap is considered a necessity for a condensate line on most HVAC systems.
Household drain piping is vented to atmosphere and can not be under negative pressure here. Pipe internal total pressure must be equal, atmospheric, at both sides of the trap..
A condensate line ideally should drain without looping, meaning it should have a consistent downward slope to ensure proper water flow and prevent potential clogs caused by water pooling in a loop; however, depending on the layout of your system, a small loop might be necessary, but it should be minimized and designed to avoid trapping water.
This is more-correct and it is what I practice.
No comments:
Post a Comment